Texas winter storm: record load shed, hospitals lose water and heat

Freezing weather knocked out generation and forced the largest controlled load shed in US history. Power loss spread to water systems and hospitals, and to patients at home on powered medical equipment.

PathPower → Devices → Human handoff

Sources checked when written 26 September 2026

TierA hospital lost water pressure and heat and began moving patients; power was shed across the grid. How tiers are assigned.

What happened

FERC and NERC reported that during the week of 14 February 2021, ERCOT averaged 34,000 MW of generation outages for more than two days, nearly half its all-time winter peak load. The controlled firm load shed of 23,418 MW was the largest in US history. The joint inquiry's recommendations include gas–electric coordination and mapping critical interdependent natural gas and electric infrastructure. Power loss stopped water treatment. In Austin, St David's South Austin Medical Center lost water pressure and heat because its boiler depended on water, and began moving patients. Its CEO said no single hospital could take a large number of transfers. Galveston and Houston hospitals also reported water problems, and about 800 people sheltered in Southeast Texas emergency departments seeking oxygen refills and power for home medical equipment. The Texas Department of State Health Services confirmed 246 storm-related deaths. Twenty-five of them (10.2%) were from exacerbation of pre-existing illness, linked to disruption of dialysis or oxygen, frozen medical devices and medication, and loss of power to life-sustaining equipment.[1,2,3,4,5,6]

Documented harm

246 deaths confirmed as storm-related by Texas DSHS, including 25 from exacerbation of pre-existing illness tied to dialysis or oxygen disruption and loss of power to life-sustaining equipment. The hospital-level harm is not separately quantified.

What it teaches

  • A hospital with working generators can still lose heat because the boiler depends on city water.
  • Grid load-shed lists that leave fuel supply unprotected turn a power problem into a fuel problem.
  • Regional events remove the transfer destinations your plan assumed.
  • Hospital generators protect electricity, not the water, gas and heating that depend on the grid.
  • In a region-wide event the transfer plan fails because every neighbour is degraded at once.
  • Patients on home devices become ED patients when the grid fails.
  • Infrastructure interdependencies (gas → power → water) have to be mapped explicitly.

Sources

  1. The February 2021 Cold Weather Outages in Texas and the South Central United States — FERC, NERC and Regional Entity Joint Staff Report (presentation of findings). FERC / NERC, November 2021. Primary Official report · link checked 2026-11-02
  2. Austin hospitals lose water pressure and heat amid winter storm. The Texas Tribune, 17 February 2021. Secondary Journalism · link checked 2026-11-02
  3. February 2021 Winter Storm-Related Deaths – Texas. Texas Department of State Health Services, 31 December 2021. Primary Official report · link checked 2026-11-02
  4. The February 2021 Cold Weather Outages in Texas and the South Central United States — Tracking of Responses to Recommendations. FERC (with NERC and Regional Entity staff), December 2022. Primary Official report · link checked 2026-11-02
  5. Boil-Water Advisory in Effect, Low Water Pressure Impacts Austin Hospitals. Circle of Blue, 18 February 2021. Secondary Journalism · link checked 2026-11-02
  6. Texas' power outages, water shortages put bigger strain on hospitals. ABC News, 18 February 2021. Secondary Journalism · link checked 2026-11-02

Power interruptions at the SPMS data centre take Portugal's national e-prescribing and electronic health record offline

On 19 October 2026, two successive power interruptions at the data centre run by SPMS, the Ministry of Health's shared-services body, left SNS information systems unavailable for several hours. Doctors could not issue electronic prescriptions or consult electronic records, and pharmacies had limited access to prescriptions.

PathPower → Connectivity & data

Two power outages knock out Kemptville hospital's EHR, internet and cellular service and their backups; ambulances diverted

On 13 October 2026 two power outages knocked out Kemptville District Hospital's cellular service, internet, electronic health record and its downtime and backup systems. The hospital declared a code grey, moved to paper, asked lower-acuity patients to go elsewhere and diverted ambulances.

PathPower → Connectivity & data → Human handoff

Prague Central Military Hospital: power cut and failed backup pause operations

Doctors told Seznam Zprávy that a power cut at Prague's Central Military Hospital, which backup generators did not adequately cover, paused all operations for about 20 minutes and left ventilators running on internal batteries. The hospital said the interruption lasted several minutes and did not affect patients' health.

All incidents · Power · Cascades · Devices · Human handoff

Information only, not advice. FailSystems is an aggregation and synthesis of published sources. It is not consulting, engineering, legal, regulatory or medical advice, and using it creates no professional relationship. Health systems are complex and no approach fits every organisation: anything you adopt is your own decision, at your own risk, and should be checked against the current official sources and by qualified people who know your setting. Full disclaimer.

Dealing with an incident right now? This site is a reference, not an incident-response service. Activate your organisation's emergency operations plan and incident command, and: