Basement flood cuts power at Jefferson Methodist Hospital, Philadelphia; hospital evacuated

Flooding in the basement of Jefferson Methodist Hospital caused a power outage on the evening of 19 May 2026, and the hospital was evacuated overnight. A police official told NBC10 that the backup generators had failed. The hospital's CEO described running on partial commercial and partial generator power.

Sources checked when written 28 November 2026

TierThe sources document a flood-caused loss of power and air conditioning, a police official's statement that backup generators failed, and an overnight evacuation of the hospital. How tiers are assigned.

What happened

According to the Philadelphia Inquirer, Philadelphia Police Chief Inspector Scott Small told NBC10 that about three feet of water flooded the hospital's basement, causing a power outage around 6 p.m. on Tuesday, and that the backup generators had failed. Patch, also citing NBC10, reported that the water caused the backup generators located in the basement to fail. The hospital said the cause appeared related to an external water source and was still being investigated. Jefferson Health CEO Joseph Cacchione told 6abc that the flood shut off the air conditioning and that the hospital was running on 'partial commercial and partial generator' power for life-support equipment. The sources do not reconcile these two accounts of the generators. The hospital was evacuated starting around 10:15 p.m., according to 6abc. 6abc reported roughly 190 patients in the hospital and more than 100 moved, mostly within the Jefferson system, with about 15 still to go. The Inquirer and Patch report about 120 people evacuated, transferred to nearby facilities or discharged. 6abc reported power restored as of 5:30 a.m. on Wednesday. The emergency department stayed open to walk-ins, with anyone needing admission taken to another hospital. Patch reported, citing Jefferson Health, that the hospital reopened the following Saturday with approval from the Pennsylvania Department of Health. 6abc reported no injuries.[1,2,3]

Documented harm

none documented; 6abc reported no injuries

What it teaches

  • Generators and switchgear in basements share a single flood exposure with the utility supply they are meant to back up.
  • Losing air conditioning can force an evacuation even when some electrical supply is maintained.
  • Reopening after a power event can depend on a regulator's approval, which should be built into recovery timelines.

Sources

  1. Methodist Hospital temporarily closed after power outage. The Philadelphia Inquirer, 20 May 2026. Secondary Journalism · link checked 2026-11-28
  2. Power restored after issues force evacuation at Jefferson Methodist Hospital in South Philadelphia. 6abc (WPVI-TV), 20 May 2026. Supporting Journalism · link checked 2026-11-28
  3. Hospital Reopens After Power Outage Forced Patient Evacuations In Philadelphia. Patch, 26 May 2026. Supporting Journalism · link checked 2026-11-08

Main generator at Gaza's Al-Rantisi children's hospital stops; Health Ministry says vital services halted and a smaller generator cannot cover intensive care

On 25 November 2026 the Ministry of Health in Gaza said the main generator at Al-Rantisi Children's Hospital had stopped suddenly, halting a number of vital medical services and, according to Anadolu's Arabic report, the operating rooms of the neighbouring Eye Hospital. The ministry said repairs were hampered by a complete absence of oils and spare parts.

Lexington, Massachusetts nursing home evacuated after recurring electrical failure; building de-energised

On the night of 24 October 2026 more than 100 residents were evacuated from a nursing and rehabilitation centre in Lexington, Massachusetts, after electrical problems that had recurred over several days. Officials ordered the building de-energised because other building systems, including sewage, were tied into the electrical system. Residents had returned by mid-November, Boston 25 News reported.

Power interruptions at the SPMS data centre take Portugal's national e-prescribing and electronic health record offline

On 19 October 2026, two successive power interruptions at the data centre run by SPMS, the Ministry of Health's shared-services body, left SNS information systems unavailable for several hours. Doctors could not issue electronic prescriptions or consult electronic records, and pharmacies had limited access to prescriptions.

PathPower → Connectivity & data

Two power outages knock out Kemptville hospital's EHR, internet and cellular service and their backups; ambulances diverted

On 13 October 2026 two power outages knocked out Kemptville District Hospital's cellular service, internet, electronic health record and its downtime and backup systems. The hospital declared a code grey, moved to paper, asked lower-acuity patients to go elsewhere and diverted ambulances.

PathPower → Connectivity & data → Human handoff

Prague Central Military Hospital: power cut and failed backup pause operations

Doctors told Seznam Zprávy that a power cut at Prague's Central Military Hospital, which backup generators did not adequately cover, paused all operations for about 20 minutes and left ventilators running on internal batteries. The hospital said the interruption lasted several minutes and did not affect patients' health.

All incidents · Power

Information only, not advice. FailSystems is an aggregation and synthesis of published sources. It is not consulting, engineering, legal, regulatory or medical advice, and using it creates no professional relationship. Health systems are complex and no approach fits every organisation: anything you adopt is your own decision, at your own risk, and should be checked against the current official sources and by qualified people who know your setting. Full disclaimer.