Incident

Guy's and St Thomas': heatwave cooling failure takes down both data centres

On the UK's record-heat day, air conditioning failed at one of the trust's two data centres and storage failed at the other. Clinical IT went down and the trust ran on paper for weeks.

Fact-checked 4 November 2026

TierData-centre cooling failed and the trust ran a 'Paper Hospital' for several weeks; the trust's review describes an IT failure and reports no loss of power to clinical areas. How tiers are assigned.

What happened

On 19 July 2022 (London peaked at 40.3°C) condenser high-pressure trips shut down cooling at the Guy's data centre, which reached 50.3°C; the St Thomas' data centre suffered disk and controller failures. The two sites were each other's backup, a design the trust's review said could not cover a shared environmental cause. Cooling concerns had been raised in 2018 and a £195k replacement request from March 2022 was still unapproved. The remote environment monitoring for St Thomas' was hosted on the storage network that failed, and email alerts stopped. The trust declared a critical incident and moved to a 'Paper Hospital'. IT recovery took several weeks before near-complete restoration, slowed by 371 interlinked systems; the critical incident was stood down on 21 September 2022. In the weeks ending 24 and 31 July, activity fell to 64% of the historic July average for referrals and 68% for diagnostic tests. The same heat caused a cooling failure in a Google Cloud London zone that day.[1,2]

Documented harm

As of January 2023: one moderate harm (a patient could not be transplanted when organs became available), 20 low harms, no deaths or severe harm identified; the harm review remained open.

What it teaches

  • Two data centres a few miles apart are one failure domain for weather.
  • Monitoring that runs on the system it watches goes dark when you need it.
  • Deferred cooling replacement is a clinical risk, not just an estates line item.

Sources

  1. Review of the Guy's and St Thomas' IT Critical Incident — Final report from the Deputy Chief Executive Officer. Guy's and St Thomas' NHS Foundation Trust, January 2023. Primary Official report · link checked 2026-11-02
  2. Incident: cooling related failure in one of our buildings that hosts zone europe-west2-a. Google Cloud Service Health, 19 July 2022. Primary Official report · link checked 2026-11-02

Power interruptions at the SPMS data centre take Portugal's national e-prescribing and electronic health record offline

On 19 October 2026, two successive power interruptions at the data centre run by SPMS, the Ministry of Health's shared-services body, left SNS information systems unavailable for several hours. Doctors could not issue electronic prescriptions or consult electronic records, and pharmacies had limited access to prescriptions.

PathPower → Connectivity & data

Two power outages knock out Kemptville hospital's EHR, internet and cellular service and their backups; ambulances diverted

On 13 October 2026 two power outages knocked out Kemptville District Hospital's cellular service, internet, electronic health record and its downtime and backup systems. The hospital declared a code grey, moved to paper, asked lower-acuity patients to go elsewhere and diverted ambulances.

PathPower → Connectivity & data → Human handoff

Manzanillo maternity hospital's backup microsystem and generator fail together during Cuban grid outage

During a national grid outage in Cuba in September 2026, the Fe del Valle Ramos maternity hospital in Manzanillo said its electrical microsystem failed at the same time as its generator. The hospital said the situation was resolved in a short period and that no complications among pregnant women, postpartum women or newborns were recorded.

All incidents · Power · Connectivity & data · Cascades

Information only, not advice. FailSystems is an aggregation and synthesis of published sources. It is not consulting, engineering, legal, regulatory or medical advice, and using it creates no professional relationship. Health systems are complex and no approach fits every organisation: anything you adopt is your own decision, at your own risk, and should be checked against the current official sources and by qualified people who know your setting. Full disclaimer.

Dealing with an incident right now? This site is a reference, not an incident-response service. Activate your organisation's emergency operations plan and incident command, and: